Analyzing the Impact of Short-Term Cyclic Thermal Ageing on PVC Insulated Low Voltage Samples with Polarization/Depolarization Current Measurement
Bal, Semih
Tamus, Zoltan Adam
2025-10-22T13:04:04Z
2025-10-22T13:04:04Z
2023
1785-8860
hu_HU
http://hdl.handle.net/20.500.14044/35014
Cables are critical elements of the network. Therefore, their integrity is of utmost
importance. Many factors influence the insulation integrity of the cables, such as
manufacturing procedures, operating conditions, and various stresses, during their lifetime.
Increasing the number of renewables resulted in increased distributed generation, which may
cause reverse power flow. The electricity demand is constantly growing with the increased
number of novel appliances on the consumer side, electric vehicles, etc. This fact can create
short-term overloads, which may cause a temperature elevation beyond the cable's maximum
operating limit, compromising insulation degradation. Therefore, this research investigates
the impact of short-term cyclic thermal ageing on SZRMtKVM-J 4 x 6 mm PVC insulated low
voltage cable using the polarization/depolarization current measurement (PDC).
Accelerated thermal ageing tests were performed by placing the samples inside the
temperature-controlled oven for 6 hours/round. After each round, the polarization and
depolarization currents were measured. DIRANA Dielectric Response Analyzer by Omicron
has been employed for the measurements. The results have shown an increase in the
polarization and depolarization current.