JavaScript is disabled for your browser. Some features of this site may not work without it.

Analyzing the Impact of Short-Term Cyclic Thermal Ageing on PVC Insulated Low Voltage Samples with Polarization/Depolarization Current Measurement

Thumbnail
Megtekintés/Megnyitás
Bal_Tamus_138.pdf (1.036MB)
Metaadat
Teljes megjelenítés
Link a dokumentumra való hivatkozáshoz:
http://hdl.handle.net/20.500.14044/35014
Gyűjtemény
  • 3.2. 2023 Volume 20, Issue No. 9. [16]
Absztrakt
Cables are critical elements of the network. Therefore, their integrity is of utmost importance. Many factors influence the insulation integrity of the cables, such as manufacturing procedures, operating conditions, and various stresses, during their lifetime. Increasing the number of renewables resulted in increased distributed generation, which may cause reverse power flow. The electricity demand is constantly growing with the increased number of novel appliances on the consumer side, electric vehicles, etc. This fact can create short-term overloads, which may cause a temperature elevation beyond the cable's maximum operating limit, compromising insulation degradation. Therefore, this research investigates the impact of short-term cyclic thermal ageing on SZRMtKVM-J 4 x 6 mm PVC insulated low voltage cable using the polarization/depolarization current measurement (PDC). Accelerated thermal ageing tests were performed by placing the samples inside the temperature-controlled oven for 6 hours/round. After each round, the polarization and depolarization currents were measured. DIRANA Dielectric Response Analyzer by Omicron has been employed for the measurements. The results have shown an increase in the polarization and depolarization current.
Cím és alcím
Analyzing the Impact of Short-Term Cyclic Thermal Ageing on PVC Insulated Low Voltage Samples with Polarization/Depolarization Current Measurement
Szerző
Bal, Semih
Tamus, Zoltan Adam
Megjelenés ideje
2023
Hozzáférés szintje
Open access
ISSN, e-ISSN
1785-8860
Nyelv
en
Terjedelem
15 p.
Tárgyszó
pvc insulation, thermal ageing, pdc measurement, polarization/ depolarization current
Változat
Kiadói változat
Egyéb azonosítók
DOI: 10.12700/APH.20.9.2023.9.5
A cikket/könyvrészletet tartalmazó dokumentum címe
Acta Polytechnica Hungarica
A forrás folyóirat éve
2023
A forrás folyóirat évfolyama
10. évf.
A forrás folyóirat száma
9. sz.
Műfaj
Tudományos cikk
Tudományterület
Műszaki tudományok - anyagtudományok és technológiák
Egyetem
Óbudai Egyetem

DSpace software copyright © 2002-2016  DuraSpace
Kapcsolat | Visszajelzés