This paper presents some common mistakes which should appear during partial
discharge measurements in ca se of high voltage capacitors. The partial discharge
measurements are a very sensitive measurement type, which have to be done in a shielded
chamber. This kind of measurement should be disturbed by conducted low frequencies
electromagnetic noises. For example the switching power supply of a Computerized
Numerical Control machine, produce a high level electromagnetic noises, which some
times is higher than the partial discharge produced by high voltage capacitors. Another
kind of mistakes which should appear is the poor cable connections in the measurement
system, which determines some discharges which appear at poor cable connections. This
kind of mistake determine a very high amount of partial discharge measurement results.
This kind of mistakes determine false measurement result or make impossible the
measurement process, which affect the credibility of the measurement laboratory.
- Cím és alcím
- Mistakes During Partial Discharge Measurements of High Voltage Capacitors
- Szerző
- Istók, Róbert
- Megjelenés ideje
- 2024
- Hozzáférés szintje
- Open access
- Konferencia címe
- XXXIX. Kandó Konferencia
- Nyelv
- en
- Változat
- Kiadói változat
- A cikket/könyvrészletet tartalmazó dokumentum címe
- XXXIX. Kandó Konferencia 2023 Kiadvány kötet
- A forrás folyóirat éve
- 2024
- ISBN, e-ISBN
- 978-963-449-357-0
- Műfaj
- Konferenciaközlemény
- Tudományterület
- Műszaki tudományok - villamosmérnöki tudományok
- Egyetem
- Óbudai Egyetem